“Stripping of Forms

(Minimum Waiting Period After Placing Concrete)

Average Temperatures

Structural
Member

Above 60°F. 500-60°F,

jess than

*Bottom forms of

OvF.

slabs spanning 6
feet or less

5 days

9 days

14 days

girders and beams

14 days

18 days

21 days

Bottom forms of

za.

*For slab spans more than 6 feet add 12 hours for each
additional foot over 6 feet.
(Except roof slabs - see
paragraph 3. below.)
3.

StrippingRoof Forms:

Roof section

forms shall not be stripped until concrete has developed

& compressive strength of not less than 2000 pounds
per square inch.
One or more test cylinders, as desired,
shall be taken of each roof section poured.
Cylinders
shall be tested in compliance with paragraph 5-07 e.

preceeding,

or as specifeid by the Engineer.

4,

Filling Tie-Rod or Bolt Holes:

Holes

remaining from bolts or the tie rods shall be filled
solid with cement
mortar. Holes passing entirely

through the wall shall be filled from inside face with
a device that will force the mortar through to the
outside face using a stop held at the outside wall
surface to ensure complete filling.
Holes which do
not pass entirely through the walls shall be packed
thoroughly full. All excess mortar at the face of
filled holes shall be struck off flush.
5-27.

REINFORCING STEEL:

&.
General:
The reinforcing, fabricated to
shapes and dimensions shown, shall be placed where
indicated on drawings or reasonably required to carry
out the intent of the drawings and specifications.

Before placing,

all reinforcement shall be thoroughly

cleaned of rust, miil scale or coatings, which would
reduce or destroy the bond.
Reinforcement appreciably
reduced in section shall not be used.
Following any
substantial delay in the work, previoualy placed
reinforcement, left for future bonding, shall be
5-19