diagrams and schedules on the drawings for the sizes of ail
circuit breaker units.
f.

Every effort will be made to check stub-ups and

power outlet locations with available equipment which is
provided and installed.

16-31.

MISCELLANEOUS WIRING:

All miscellaneous equipment 1:

stallation and wiring called for on the plans shall be pro-

vided.

16-32.
REFERENCE PUBLICATIONS:
Any of the following publications which are available can be used for further referenc

on this subject:

a. American Electrician's Handbook by Terrell Croft
published by McGraw-Hill.

b.

War Department Technical Manual TM-5-680B, In-

terior Electric Systems, Repairs and Utilities, Electrical
Facilities,
16-33.

SHIELDED ROOMS:

a.

Furnish and install double shielding for areas

indicated on the drawings including Building No. 116 at Lo-

cation "A,"
b.

Zinc-coated steel mesh, 8 x 8 size, 0.0173 inche

diameter steel, weighing not less than 23.5 pounds per 100
square feet shall be applied to floor, ceiling and all four

walls,

on both the inside and outside face of studs.

Six-

teen (16) ounce sheet copper shall be installed at door oper
ings.

c.

All joints between sections of mesh, between se:

tions of mesh and copper,

and between sections of copper

shall be continuously and solidly soldered.

a.
Details of connections to ground and at doors ar
windows shall be completed in accord with details on the
drawings.

16-13

Select target paragraph3