shall bear the manufacturer's nameplate and the underwriters' inspection label. 16-30. POWER WIRING: This Contractor shall furnish and install all wiring and shall completely connect all motors on pumps, fans, compressors and similar equipment. All motors will be furnished and set by others. Motor starters will be furnished by others but shall be installed and completely connected by this Contractor. All line voltage wiring required for the control of motor driven equipment will be furnished and installed by this Contractor. a, Power Switchboards: All power switchboards shall be equipped with circuit breaker units and shall be of dead front, unit type, formed steel construction. Indi- vidual cubicles shall be die-formed and equipped with standard closing plates. The finish shall be one coat of prime: and two coats of grey synthetic enamel. its shall be 3-pole, 600-volt, WL, as required, or equal. Circuit breaker un- Square D Company, Type ML or b. Power Panelboards: Power panelboards shall be equipped with circuit breaker units housed in code gauge galvanized steel boxes providing wiring gutters four ( ) inches wide or larger, as required. The finish shall be one coat of primer and two coats of gray synthetic enamel. Circuit breaker units shall be 3-pole, 600-volt, Company Type ML or WL, as required, or equal. c. Square D Separately mounted circuit breakers where shown on the drawings shall be 3-pole, 600-volt breakers in NEMA 1, Sheet steel enclosures, Square D Company Type ML or WL as required, or equal. d. Motor-Disconnect Means: Each motor shall %e provided with a disconnecting means when required by the National Electrical Code even though not indicated on the drawings. A circuit breaker or horsepower-rated switch in & panelboard will be acceptable as a disconnecting means, if located in the same room or within sight of the motor controller. A quick-make and quick-break general-use tumbler or snap switch will be acceptable for capacities less than 30 amperes, provided the ampere rating of the switch is at least double the rating of the controlled equipment. Switches of 30- to 400-ampere capacity shall be of the enclosed, quick-make and quick-break type, horsepower-rated. Switches shall disconnect all ungrounded conductors. e. This Contractor shall refer to the single line 16-12