openings as desired and shall be secured in closed posi-

tion by loose pin fastening
When installing hinge
clevices care shall be taken to see that clevis and bolts
are pushed against top of hole in girt before tightening,
to avoid shutter arm projecting beyond wall face when in
Closed position.

In no case shall arms, when closed or

while closing, project beyond the interior face of wall
girts. Where called for, openings shall be provided with
frames covered with plastic mesh screening or plastic

glass, as specified in "Carpentry and Related Work"
section.

1.

Interior Partitions:

Intertor partitions as

furnished by the building manufacturer shall be 6 feet 9

inches in height and shall consist of corrugated panels

set in extruded posts and rails.

Full height posts,

at

intervals shown shall be connected to roof purlins.
Partitions shall normally be open for lower 15 inches; where

required, special filler panels shall be provided to close
to floor.
Partition posts shall be secured to floor slab
dy shot bolts through aluminum foot castings.
Partitions,
partition caps, full height posts, etc. shall be saw-cut
to size in the field where required.
Wooden partition
panels, where called for on the drawings or directed by the

Engineer, shall conform to the provisions of the "Carpentry and Related Work" section.
j.
Fixture Supports:
Supports for mechanical
and electrical fixtures shall consist of aluminum plates
bolted or clipped to the building construction and shall
be installed where shown or required.
Cooperate with
mechanical and electrical tradesmen to install support
plates in proper locations for the work.
Supports where

wooden partition panels are used shall be in accordance

with the provisions of the "Carpentry and Related Work”
section,

k. Weatherproofing:
Openings between roof
construction and eave struts shall be filled with shaped
sponge rubber plugs.

Where required for air conditioning

purposes similar plugs shall be installed in wall construction.

1.

Special Details:

Building manufacturer shall

furnish special connecting and gutter sections for "L" and

"T" shaped building design and for parallel connections in

accordance with details shown on the drawings.

Manufactur-

er's standard weather hoods for pedestrian doors and canopies built up of manufacturer's standard sections shall be