HAWALL,
F&SNO.

17004
USER

UNA LOA

SCIENTIFIC AND SUPPORT

TITLE

Power
STRUCTURE. FACILITY NO.

JTF

SCIENTIFIC STATION NO.

None

BOD

None
FOD

FUNDING
AGENCY

AEC

($000)

ENGR

PRE-GO
Prior Cost

PROC

CONST

Included in F&S Nos.

TOTAL

FURN

17002 and 17005

PRIOR YEARS
ENGINEERING
Drawings:

Completed.
JS 104-069-F4

F 104-069-El

JS 104-069-E7

JS 104-071-E2

JS 104-069-E9

F 104-080-El and E2

PROCUREMENT

Completed.

CONSTRUCTION

The Hilo Electric Company's transmission line serves the

Mauna Loa site with 12.4 kv power.

A 120/208-12,400 volt,

75 kva,

3 phase

transformer transforms the incoming power for use by the AEC facilities. A
90 kw diesel generator serves as a back up source of power in the event of
commercial power failure. Generator start-up and transfer of power is

manually effected.(Completed in 1967.)

Experience has shown that the present generator at the Mauna Loa site is
inadequate. This 90 kw generator was derated to 60 kw capacity primarily
due to the great altitude of the site, but actually encounters difficulty in
providing an output of 45 kw. The generator will be replaced with a larger
unit capable of providing satisfactory backup capability and with less erratic
fluctuations in voltage and frequency.