d.

Tests and Inspections.
1..

All portable and fixed fire extinguishers should be

examined monthly to make certain that they have not been tampered with, and have

not suffered corrosion or damage.

Seals should be inspected to determine that

the extinguishers have not been operated since last being charged.
ll.

Extinguishers shall be recharged after use, even though

only partially discharged.

A record of inspections shall be maintained and the

equipment so tagged.
|

iii.

Foam extinguishers shall be recharged annually. Dry

chemical extinguishers shall be weighed annually, and should be shaken

:

semiannually to avoid packing. . All other cylinders shall be weighed annually.
iv.

All portable and fixed pressurized cylinders shall be

hydrostatically tested and inspected internally at intervals not to exceed five
years.

‘4.

ELECTRICAL
a.

Electrical Equipment
All electrical equipment shall comply with U.S. Coast Guard

Electrical Regulations.
b.

Batteries
Lead acid batteries,

or equivalent,

shall be properly se-

cured in a acid proof tray and the terminals protected against accidental
contact by tools and other gear.

Polarity check indicators should be utilized

when using dock side power for battery charging.
ventilated and "No Smoking" signs posted.

9008625

Battery compartment shall be