c.
Partitions, Walls and Ceilings.
Dry wall partitions
are recommended.
Finish on walls should be washable.
Light
pastel colors are acceptable except that light yellow should

be avoided in the doctor's and technician's office, the
emergency room and the ward. White is recommended for the
emergency room.

Specifications for lead lining the x-ray

area is included in Atch 4.
The sterilizer partition should
be insulated to keep heat generated by sterilizer from moving
into the emergency room.

d.
Plumbing and Sinks.
Install and plumb sinks in areas
indicated on the attached sketches of the clinic and aid
station floor plan.
Sinks in the emergency rooms should be

equipped with knee operated faucets and plaster traps.
Faucets with threads for a hose connection should be provided on the exterior wall near the emergency room entrance
at both the clinic and aid station.
e.
Doors.
Double entry doors are not required but are
satisfactory if existing.
A 3' 10" single door at entry

penetrations is adequate.

A minimum door width of 40" is

required to move x-ray room equipment in and out of the
building.
The door to the sterilizer room should be vented.
f.

Electrical Power Requirements.

(l)

Electrical requirements for the x-ray, dental

operating unit and sterilizer are shown in the attachment
describing these items.
(See Atch 4).
(2)
Wall outlet receptacles should be 115V AC, 60Hz,
15Amp single-phase duplex outlets--no more than two on any
branch circuit.
Locations for electrical outlets are shown
on the floor plan for the Lojwa medical aid station and in
the detailed sketches of the separate rooms in the Enewetak
Clinic.
(See Atchs 2, 4 & 5).
Location of electrical outlets in the administrative and waiting areas of the Enewetak
Clinic are shown in Atch l.

g.Emergency Electrical Power.
The clinic should be
wired to permit hook-up of an alternative source of electrical
power.

A stand-by generator of sufficient size to operate the

X-ray and emergency equipment and light exit signs must be
made available in the event the primary electrical power
supply fails.
h.

Lighting.

Lighting is required in accordance with

Standards as listed in AFR 88-50.

Requirements for the

various patient care and service areas have been extracted
from the regulation and are included as Atch 3.
Include
sufficient lighting in the rooms to meet these standards.