c. Partitions, Walls and Ceilings. Dry wall partitions are recommended. Finish on walls should be washable. Light pastel colors are acceptable except that light yellow should be avoided in the doctor's and technician's office, the emergency room and the ward. White is recommended for the emergency room. Specifications for lead lining the x-ray area is included in Atch 4. The sterilizer partition should be insulated to keep heat generated by sterilizer from moving into the emergency room. d. Plumbing and Sinks. Install and plumb sinks in areas indicated on the attached sketches of the clinic and aid station floor plan. Sinks in the emergency rooms should be equipped with knee operated faucets and plaster traps. Faucets with threads for a hose connection should be provided on the exterior wall near the emergency room entrance at both the clinic and aid station. e. Doors. Double entry doors are not required but are satisfactory if existing. A 3' 10" single door at entry penetrations is adequate. A minimum door width of 40" is required to move x-ray room equipment in and out of the building. The door to the sterilizer room should be vented. f. Electrical Power Requirements. (l) Electrical requirements for the x-ray, dental operating unit and sterilizer are shown in the attachment describing these items. (See Atch 4). (2) Wall outlet receptacles should be 115V AC, 60Hz, 15Amp single-phase duplex outlets--no more than two on any branch circuit. Locations for electrical outlets are shown on the floor plan for the Lojwa medical aid station and in the detailed sketches of the separate rooms in the Enewetak Clinic. (See Atchs 2, 4 & 5). Location of electrical outlets in the administrative and waiting areas of the Enewetak Clinic are shown in Atch l. g.Emergency Electrical Power. The clinic should be wired to permit hook-up of an alternative source of electrical power. A stand-by generator of sufficient size to operate the X-ray and emergency equipment and light exit signs must be made available in the event the primary electrical power supply fails. h. Lighting. Lighting is required in accordance with Standards as listed in AFR 88-50. Requirements for the various patient care and service areas have been extracted from the regulation and are included as Atch 3. Include sufficient lighting in the rooms to meet these standards. 2