je one subbase.

Each pump capacity shall be 3 G.P.M.

against 20 p.s.i. discharge pressure.

Motors shall be 1/2

HP., 220 volt, 1 phase, 60 cycle pumping unit shall not ex-

ceed 1750 R.P.M. Float switches shall have automatic alternator to alternate operation of pumps and to start second pump
if first pump fails to handle the load. Pumping unit shall

be Chicago Pump Company, Fig. 3027 using type "N" pumps with
gate valves or approved equal,

k, Thermometer. The thermometers shall be the Angle
Mercury Bulb type. The temperature range shall be from 30° P

to 300° F, The thermometers shall be Gotham Type A~S-2635-12
inch, Tag 3),02-1/2-12 inch or approved equal.
1. Tank, The 3000 gallon fuel oil storage tank shall be

as indicatedon H & N Sketch No, SK-lj16,

m, Flexible Connection. The flexible connection for engine exhaust shall be as indicated on H & N Sketches Nos.SK-~

W12—1, SK-h28, SK-429-1 and SK-l.29-2.

n. Butterfly Valves. The butterfly valves shall be suitable for exhaust gas at 1509 F., working pressure 25 p.eSehe,

leakage not over 1/2 of 1%.

125-pounds American Standard,

Valve flange drilling shall be

Val ves shall be installed in

vertical line. Valves at top of silencer shail have chain
wheel control with chain to hand down ten (10) feet below
wheel standard hand lever control for valves at bottom of
silencer. Valves shall be W.S. Rockwell Company Bulletin No.
502, or approved equal and shall be of the sizes indicated on
the drawings.

20-06, INSTALLATION OF EQUIPMCNT:
a, General. All pieces of equipment shall be mounted
on their respective foundations or supports. Foundations
for equipment shall be as shovm on structural drawings or as
indicated on Power and Distilled Water Plant drawings. Those
which are mounted on concrete foundations shall be accurately leveled with suitable wedges or jacks, and shall be bedded in grout consisting of one part cement and two parts sand

to a minimum thickness of 1/2 inch.

The grout shall fill

all pipes around foundation bolts. After the grout has
thoroughly set, the wedges or jacks shall be removed and all
foundation bolt nuts shall be tightened down before making
any pipe connections to the eqiipment,.

20-5