after stranding shall meet all requirements of A.S.T.M,
Standard Specifications for Soft Annealed Copper Wire

(B-3) and Bare Concentric-Lay Copper Cable (B-8).

INSULATION:

Each conductor shall be insulated with 4
a.
colored, thermoplastic, synthetic insulating compound
that meets all requirements of the latest issue of

U.S.C.G. Master Specifications No. S-255,

and the

electrical requirements of this specification.

b.
The insulation shall have an average
diameter of not less than 0.176 inch and a minimum
wall thickness of 0.045 inch.
The colors used shall
be in accordance with Table I.

CABLING:
a.

Two insulated conductors shall be laid up

splrally with a sultable right hand lay to form a core
over which elght additional insulated conductors shall
be laid up spirally with a suitable left hand lay.
All intersplices shall be filled with cutched jute to

form a smooth round cable, over which shall be applied
& suitable cotton tape containing not more than 30% by

volume of reclaimed rubber and no crude rubber.
The
tape shall be frictioned on one side only, applied with
the plain side in, with an overlap of approximately

20% of the width of the tape.
b.

The colors of the individual conductors

shall be in the order indicated in Table I.
When
placed on reels for final delivery, the colors as
tabulated when viewed facing the outer end of the cable

on the reel,

shall appear in a clockwise order.

Table I
Core - - +--+ - = 7 -- Outer layer - ------.

White, black
Red, black, green, black,

blue, black, orange, black.

JACKET:

&. A jacket of thermoplastic,
synthetic compound
shall be applied over the taped core.
the compound
employed shall meet all requirements of the latest issue
of U.5.C.G. Master Specifications No. S--255.
The jacket

shall have an average outside diameter of 0.906 inch
18-2