diagrams and schedules on the drawings for the sizes of ail circuit breaker units. f. Every effort will be made to check stub-ups and power outlet locations with available equipment which is provided and installed. 16-31. MISCELLANEOUS WIRING: All miscellaneous equipment 1: stallation and wiring called for on the plans shall be pro- vided. 16-32. REFERENCE PUBLICATIONS: Any of the following publications which are available can be used for further referenc on this subject: a. American Electrician's Handbook by Terrell Croft published by McGraw-Hill. b. War Department Technical Manual TM-5-680B, In- terior Electric Systems, Repairs and Utilities, Electrical Facilities, 16-33. SHIELDED ROOMS: a. Furnish and install double shielding for areas indicated on the drawings including Building No. 116 at Lo- cation "A," b. Zinc-coated steel mesh, 8 x 8 size, 0.0173 inche diameter steel, weighing not less than 23.5 pounds per 100 square feet shall be applied to floor, ceiling and all four walls, on both the inside and outside face of studs. Six- teen (16) ounce sheet copper shall be installed at door oper ings. c. All joints between sections of mesh, between se: tions of mesh and copper, and between sections of copper shall be continuously and solidly soldered. a. Details of connections to ground and at doors ar windows shall be completed in accord with details on the drawings. 16-13