TO PREVENT LEAKAGE in the roof structure of alumi-

num buildings, penetration of roofing panels for cable
or conduit support bolts is not permissible.

16-07.

NON-NETALLIC SHEATHED CABLE shall be used for ex-

posed and concealed overhead branch circuit wiring for

lighting unless otherwise indicated on the drawings.

It

shall not be used as service entrance cable; nor shall it
be embedded in concrete,
16-08.
SERVICE ENTRANCE CABLE shall be used for service
equipment to service head where indicated on the drawings.

16-09. RIGID CONDUIT shall be used for underground branch
circuit wiring for power unless otherwise indicated on the

drawings.

16-10,

LAMPS:

All lamps will be furnished and installed

by this Contractor.

16-11. SYSTEMS:
Interior light and power system characteristics shall be as specified under Section 15-16 of the:
specifications.

16-12.
ORDINANCES AND REGULATIONS:
All apparatus and
material installed under this specification shall be design:
ed to comply with and shall be installed in accordance with
all of the legally constituted authorities having jurisdiction, including all rules and regulations of the Nationel
Board of Fire Underwriters.
16-13.

STANDARD PRODUCTS:

Unless otherwise indicated in

writing by the Engineer, the materials to be furnished und:
this specification shall be the standard products of the

manufacturers regularly engaged in the production of such
equipment and shall be the manufacturer's latest standard
design.

16-14,

MATERIALS AND EQUIPMENT SCHEDULES:

As soon as pra.

ticable and within thirty (30) days after the date of award
of Contract and before any material or equipment is purchased, the Contractor shall submit to the Engineer for
approval a complete list, in triplicate, of materials,
fixtures, and equipment to be incorporated in the work. Tf
list shall include catalog numbers,

16-3

cuts, diagrams,

drawing