station service transformers shall be dry type, equal to
Westinghouse Type AVR.
Outdoor distribution transformers
shall be oil immersed,

self-cooled,

15-39.

Before installing transformers,

Material Type "RW".

TRANSFORMERS:

check oil for moisture,

equal to Line

core for loose connections and

excess heating, and insulators for tightness.

15-40. When facing the direction the power is coming from,
the transformers of a three (3) phase bank shall be named
from right to left, "A", "B", "c".
15-41.

Unless otherwise indicated on the plans, primary

fuse size for single phase transformers shall be as follows

Transformer

Fuse Size

in

in_Amperes

3

5

5

5

7.5

3

10

LO

15

15

25

25

37.5

25

50

40

15

30

100

#5

150

100

SAFETY:

15-42.

Safety is of primary importance in the construc-

tion of power lines.

For this reason it is important

that the lineman understand the principles of this type
of construction.