or canvas, with a vent provided in the top for the excape of the
moisture-laden air.

The warm air must be adequately circulated over

all surfaces to be dried, and if natural draft is not sufficient to
accomplish this, small fans should be used to force circulation.
machines may be conveniently dried out by heating in an oven.

Small

Regardless

of method used, the temperature should not be permitted to exceed 90°C,
The time required for thorough drying out will depend to a considerable extent on the size and voltage of the machine, and on the method
of heating.

Insulation resistance measurements should be taken at

intervals of several hours, until the readings become fairly constant.
The normal insulation resistance value as established by AIEE Standards
is as follows:

Megohms =

Rated Volta

f

RatinginKVA + 1000
100

In event the KVA rating is not known, the Hp rating may be used to
arrive at a sufficiently accurate value for practical purposes.

Dry

machines in good condition will have an insulation resistance value
considerably higher than that obtained from the formula.

A megohmeter

offers tne simplest method of measuring this resistance as it gives a
direct reading, but the voltmeter method can be used providing a proper
direct current source is available.
DIELECTRIC TESTS
After the windings have been thoroughly dried out, and insulation
resistance readings are satisfactory, a high potential test may be
applied to determine the dielectric strength of the insulation.

New

windings should successfully withstand a high potential test of twice

3-52