JOHNSTON ATOLL
F & S$ NO.
TITLE
ed
SCIENTIFIC
,
01124
Cleansweep Motor Payload Preparation and Storage Building
USER
STRUCTURE/FACILITY NO.
LRL
SCIENTIFIC STATION NO.
709
FUNDING
AGENCY
($000)
AEC
BOD GO+30
None
ENGR
PRE-GO
Prior Cost
Estimatell/67
TOTAL
PROC
20.0
1.0
21.0
Fop GO+60
CONST
TOTAL
* 232.2
20.0
233.2
232.2
FURN
253.2
FACILITY IS IN HOLD STATUS PENDING DETERMINATION OF NEED BY LRL
ENGINEERING Preliminary design drawings have been reviewed by LRL.
Com-
ments received remain to be incorporated on drawings and resubmitted to LRL
for approval. No action will be taken while facility is in hold status.
PROCUREMENT
To be determined
CONSTRUCTION This building will be irregular in shape and consist of approximately 5130-sq. ft. of roofed area. The maximum dimensions of the building
are 101-ft. and 86-ft. with an average ceiling height of 14-ft. The exterior walls
and interior partitions will be constructed of 1-ft. thick reinforced concrete. The
roof will be steel frame with wood joists covered with l-in. sheathing and builtup roofing. A monorail system with a clear height of 12-ft. will extend throughout the building and to covered loading platforms on the east and west side of the
building.
Three dual speed electrified one ton hoists will be mounted on the mono-
tail system.
All doors in the building shall be equipped with panic hardware.
The entire facility will be air conditioned and dehumidified with all ducts entering
the rooms through the roof.
Approximately 75 kva of 120/208 volt, 3 phase, 60 cycle power will be required.
Grounding bars will be mounted on all interior walls and also at the two loading
platforms for truck grounding.
Fluorescent lights with retainer screens mount-
ed throughout the building shall be dual-rated Class I and IIA through G types.
The floor of the motor payload mating and igniter fin installation rooms will be
covered with conductive linoleum. All other floors will have a smooth concrete
finish. The building will be fitted with adequate lightning protection aml explosion proof telephones.
DRAWINGS:
91-709-Cl
91-709-Al thru A5
91-709-S1 and S2
91-709-M]1 thru M4
91-709-E1l thru E6
91-709-Wl
*Includes $11, 800 for construction of a berm on three sides of Building 709.