SECTION 18
CONTROL AND SIGNAL SYSTEM

18-01.

GENERAL CONDITIONS:

The following paragraphs

of Section 15 of these specifications shall apply to

this section: 15-01,

18-02.

SCOPE:

15-02, and 15-04.

The work to be done under this section

of these specifications shall include the furnishing of

all materiais, labor, equipment, and tools required to
complete and have ready for operation the installation
of the following items in accordance with these
specifications and the applicable drawings:
a.
Extensions and Additions to the existing
control and signai submarine cabie trunking system.
b.

The Installation of Underground Control

and Signal Cables.

18-03.
SUBMARINE CONTROL AND SIGNAL CABLE:
The submarine control and signal cable shall comply with Navy
Department United States Coast Guard Specification No.

S$-254-42, Ten-Conductor Armored Control Cable Issue —
(October 1, 1942) including Master Specifications Nosy

5-219 Inspection and Testing of Rubber-Insulated Cables,
5-235 Galvanized Armor Wire for Submarine Cable, and

S-255 Synthetic Insulation for Submarine Cables.
specification is copiled herewith.

This

GENERAL:
a.

These specifications cover the manufacture

of submarine control cable, consisting of ten No. 14
AWG stranded copper conductors, with 3/64" colored
plastic insulation, type, 5/64" plastic jacket, tape,
50 pound cutched jute serve, No.

10 BWG armor, and

16/3 ply impregnated jute outer serve.

cable.

b.

This cable shall be designated Type 115-P

CONDUCTORS:

&@.
Each conductor shall consist of 7 strands
of untinned copper wire 0.0253 inch in diameter.

Samples of the

conductor selected by the inspector

18-1