SECTION 18 CONTROL AND SIGNAL SYSTEM 18-01. GENERAL CONDITIONS: The following paragraphs of Section 15 of these specifications shall apply to this section: 15-01, 18-02. SCOPE: 15-02, and 15-04. The work to be done under this section of these specifications shall include the furnishing of all materiais, labor, equipment, and tools required to complete and have ready for operation the installation of the following items in accordance with these specifications and the applicable drawings: a. Extensions and Additions to the existing control and signai submarine cabie trunking system. b. The Installation of Underground Control and Signal Cables. 18-03. SUBMARINE CONTROL AND SIGNAL CABLE: The submarine control and signal cable shall comply with Navy Department United States Coast Guard Specification No. S$-254-42, Ten-Conductor Armored Control Cable Issue — (October 1, 1942) including Master Specifications Nosy 5-219 Inspection and Testing of Rubber-Insulated Cables, 5-235 Galvanized Armor Wire for Submarine Cable, and S-255 Synthetic Insulation for Submarine Cables. specification is copiled herewith. This GENERAL: a. These specifications cover the manufacture of submarine control cable, consisting of ten No. 14 AWG stranded copper conductors, with 3/64" colored plastic insulation, type, 5/64" plastic jacket, tape, 50 pound cutched jute serve, No. 10 BWG armor, and 16/3 ply impregnated jute outer serve. cable. b. This cable shall be designated Type 115-P CONDUCTORS: &@. Each conductor shall consist of 7 strands of untinned copper wire 0.0253 inch in diameter. Samples of the conductor selected by the inspector 18-1