16-25.

WALL RECEPTACLES:

Wall receptacles shall conform

to the requirements of Federal Specificatian W-R-15la, type

and style as specified.

Heavy-duty receptacles shall be of

the single type having capacity to carry the rated load

continuously without damage and shall be furnished with a
suitable cord-grip cap.
a.

Duplex Convenience Receptacles:

Duplex conven-

ience receptacles shall be Type II, Style No. 102, rated

10 amperes at 250 volts and 15 amperes at 125 volts.

shall be constructed of brown phenolic composition.

Bases

Ter-

minals shall be mounted on the sides of the base with two
screws per terminal.
Not more than one conductor will be
installed under one screw-head.
Duplex convenience receptacles installed in damp or wet locations and where speci-

fied shall be Type II, Style No. 130, 3-pole type designed
for grounding, rated 10 amperes at 250 volts and 15 amperes
at 125 volts. Mounting straps shall have plaster ears.
bo.

Single Flush,

3-Pole,

3-Wire,

20-Ampere,

250-

c.

3-Phase, 4-Pole, 4-Wire, 20-Ampere, 250-Volt

Volt Receptacles:
Single Flush, 2O-ampere, 250-volt receptacles shall be Type II, Style No. 153.
Receptacles:

Receptacles for 20-ampere,

service shall be Type II, Style No. 165.

250-volt,

3-phase

lL.
Junction boxes shall be National Electric
Products Corporation #7525-58, or approved equal, equipped

with #7565 standard tops.
2.

Receptacle outlets shall be National Elec-

3.

Telephone outlets shall be National -lec-

tric Products Corporation #7903-L or equal equipped with
duplex receptacles.

tric Products Corporation #7904-L or equal.
16-26.

WALL SWITCHES:

Wall switches shall be of the to-

tally enclosed tumbler type and shall conform to the re-

quirements of Federal Specification W-S-896 or W-S-893.

In addition to the spring actuating the switch, the opera=
ing mechanism shall include a positive mechanical means tv
initiate motion tending to close and/or open the circuit.
Enclosures shall be phenolic composition. Not more than
two switches shall be installed in a single gang position

of a switch box.
Single-pole three-way and four-way switc!
shall be of the tumbler type, rated 10 amperes at lehvolt:
All switches shall be suitable for the control of tungsten-

16-10

Select target paragraph3