c.

forms,

Exterior Painting Schedule:

1.

Woodwork including towers (except plat-

landings, ladders and railings), tent frames, the-

atre screen frames and supports, woodwork at theatre stage
and unpainted screen sash.
First coat shall be Dutch Boy

No. 25 "Exterior Wood Primer" reduced 10% with mineral

thinner or approved equal.
Second coat shall be aluminum
paint as specified in paragraph 2b of this section.

forms,

2.

landings,

Woodwork including theatre benches,

ladders, catwalks and railings.

plat-

First

coat shall be Dutch Boy No. 25 "Exterior Wood Primer" reduced 10% with mineral thinner or approved equal.

Second

coat shall be Dutch Boy "Nalco Synthetic Finish" color No.
5269, silver gray, reduced 10% with metal thinner or ap-

proved equal.
Third coat shall be same as second coat,
cept apply unreduced.

3.

coat shall be

Theatre Screen (asbestos-cement):

"Exterior Masonry Primer"

Wesco Water Paints,

ex-

First

as manufactured by

Inc., or approved equal.

Second coat

shall be “Durasite" as manufactured by Wesco Paints, Inc.,
or approved equal with the colors, black and white, as in-

dicated on the drawings.

4,

Structural Steel and Miscellaneous Metal

Work:
First coat shall be Dutch Boy No. 1001 Zinc Chromate
Primer or approved equal.
Second coat shall be Dutch Boy

No. 1005 "Ready Mixed" Aluminum or approved equal.

Except

where specified second coat shall be the same as first coat.
For Keystone Rust Preventative application and removal see

6-10 of these specifications.

5.
Exterior Surfaces of all Steel Banks,
Steel
and Iron Pipe, Valves and Fittings (uninsulated) and “quipment:

(a)

First coat shall be "Coro-Gard #9" zinc

(b)

Second coat shall be "Coro-Gard #14"

(c)

Third coat shall be “Coro-Gard #24"

chromate base primer,

or approved equal.

corrosion resisting coat, or approved equal.

corrosion resisting top coat, flat aluminum color (except
valves or equipment to be color coded),

6.

Color Codes:

or approved equal.

P.O.L. facilities items in-

cluding block valves on pump discharge lines, meter outlet

10-8

Select target paragraph3