DIESEL LUBE OIL COOLING AND PURIFICATION SYSTEM
DRAWING FS 430
The normal operating pressure on the lubricating system is 20-30
psi as read on G-l or G-2, and the normal operating temperature should

be 190°F as read on T-1.
The strainer is normally cleaned by turning the handles located
on the top side of the strainer.

These handles should be turned three

or four times a day; check the lubricating oil at the filter gauge.

When the oil pressure reaches 30 or 40 pounds or when the oil flow is
insufficient to keep the oil in desired condition, the filter cartridges
should be replaced.

However, once a week the strainer cartridge should

be removed and cleaned.

Remove drain plugs and allow lube oil remaining

in strainer case to drain in bucket.

Clean strainer, cartridge and case.

Replace drain plugs and cartridge.
An oil level gauge dip stick is provided at the control side of
the engine for measuring the oil level.
The lubricating oil in the system should be completely drained
and renewed at regular intervals; the time period between oil changes
depends upon engine operating conditions and the type of lubricating
oil used.
For additional care and cleaning of lube oil system refer to
Manufacturer's Instructions.