ed

out”
Att, D.

PHYSICAL FACILITICS ROCUIRED FOR THE BIOLOGICAL AFD
ETDICAL LABORATCRY TO ASSURE SATISFACTORY
GORKTYG CONDITICNS TOR THD PROGRSM

2, Buildincs:

a. Laboratory:

Two (2) units, 24' x €0' placed side by side.

Iech of these units should have a corridor 4' wide on one side of the

building; and each should then be divided into 5 basic laboratory units,
201 x 16' each, The purposes for wrich the small rooms would be used are
as follows: large animal patholo¢y, small animal pathology, blood
collection and sample oreparation, lematology, biochemistry, x-ray therapy
unit, counter and calibration of instruments, office and storage,
bh. Mouse Colony: One unit 24' x €0', without subdivisions
te house the animals, in prover cases, on nroper racks; erd one shed, 24!
x 20' ejuirned as wash house with running sca vater for waslinc, cleaning
and sterilizing the cages,

c. StorarcBuilding:

of dried food, equipment, etc.

One unit, 24' x 40' for general storage

d. Shed to cover diesel generators,
e. Shed to cover walk-in rcfrigerators,
2. Services:

a, Tro (2) 75 KN, 3 phase, 220 VAC, diesel generators,
"
b, Fresh water suoply system: a storage tank of at least
2000 cals capacity, with a distribution system; and facilities for
pumping water from water barges.
ce, Salt water sud ly system: a heavy duty pump and piping
to provide sea «ter for weshing animal facilities,

d. To (2) 900 cu, ft. wal':-in type refriccrators: one for

storing specimen carcasses; the other for fresh feed; capable of holding
contents at 35 = 40°F,

e, Three (3) Carrier deep-freezes, 9 cu fect, capable of

holding a full lozd at -55°F,

f, X-Ray therapy, 250 KV apparatus,
g. Incinerntor: cicscl oil operated, flash type for disposal
of oxcrota-soak.d shavings, cte,

h. Scuage systom:

for disposal of laboratory and human wastes;

i, “later distillation apparatus, for drinking ater:

Capacity of 500 - 1000 Gal/day.
animals,

J. Runsays, wire fencing, and half-shelters for large

3. Communications:
ag Three telephones connected with the intor-island telephone
system are required,
4. Transportation:
a, Two (2) jocps with trailers, and one weapons carricr,

b, Two (2) LCVP tyne boats.
There is no plan to have living quarters or messing facilitics on
the island with the laboratory and animal colony,