Pe
KAUAI, AEC-TRE
F&S NO.

12012
USER

SUPPORT

TITLE

Maintenance and Service Building
STRUCTURE FACILITY NO.

Sandia

SCIENTIFIC STATION NO.

None

Bop

None

FUNDING
AGENCY

($000)

ENGR

AEC

PRE-GO
FY-69
FY-71

6.4

TOTAL

6.4

PROC

CONST

TOTAL

95.1

6.4
95.1

95.1

101.5

FOD6 -30 -71
FURN

FY 1969
ENGINEERING

In progress.

Preliminary drawings issued for approval are:

JS 97-032-C2
JS 97-032-A7 thru AJ
JS 97-032-S3

JS 97-032-M3
JS 97-032-E3 and E4

FY 1971
ENGINEERING

To be completed in FY 1969.

PROCUREMENT

To be accomplished.

CONSTRUCTION A steel framed building, 30 x 44 x 14-ft. high, erected ona
concrete slab, will contain a vehicle servicing area and a maintenance shop.
The 27 x 30-ft. vehicle servicing area will be equipped with battery charging
facilities, sinks, storage facilities for grease and spare parts, and a com-

pressed air system.

A 12 x 18-ft. roll up door will provide access to the

vehicle servicing area.

The maintenance shop, 17 x 30-ft. will have gypsum board walls and ceiling,
will be insulated, air conditioned and dehumidified. Interior and exterior
lighting will be provided. Convenience outlets (110-volt) will be distributed
throughout the interior. Power supplied from a distribution panel at the

trailer dock will be 15 kw 120/208 volt, 60 cycle, 3 phase.

A 2 post hydraulic lift will be installed on an extension of the building's concrete
floor slab outside the south end of the vehicle servicing area. A gasoline pump
and an underground storage tank will be located south of the building. The building will be supplied with a fresh waterline.

12-7