Wola
NAS BARBERS POINT

SCIENTIFIC

09001

Page 3

Suspended fluorescent fixtures provide Luv foot candlesat three feet above interior floor level.

Roof-mounted, weather-proof fixtures illurminate the area

between the building and the perimeter security fence to 0.02 foot candles at
ground level.
The compressor supplies filtered air at 100 psi to hoses on wall-mounted reels
in the high-bays.
A fire-alarm system, intercom system, and telephone service to the Loading
and Maintenance Pad are provided.
Building 1682 is grounded and is protected with lightning rods.
rooms have static grounding points.

The high-bay

Substation 1684, equipped with a 750 kva, 277/480-4160 volt, 3 phase transformer, supplies power to the Assembly Building.

An additional transformer,

112 1/2 kva,- 120/208-480 volt, is located within the building.

A 30 kw diesel generator in the west equipment shelter functions as a backup
source of power. An automatic transfer switch is provided.

DRAWINGS:

F 95B-080-El, E5 and E6
F 95-1682-Al thru A8

JS 95B-075-C2
95B-077-W1 and W2

F 95-1682-Cl and C2

JS 95-1682-Al.A

F 95-1682-E] thru Ell and E14

JS 95-1682-A1.B

F 95-1682-S]1 thru S4

JS 95-1682-A2 and A3

F 95-1682-W7 thru W12

JS 95-1682-Cl

JS 95B-1682-A2 and A3

JS 95-1682-E1

JS 95B-1682-E2 and E3

JS 95-1682-W1

JS 95B-1682-Ml1 thru M3

JS 95-032-M2

JS 95B-1682-Si and $3

JS 95-032-A6

JS 95B-032-A9 and Al0

9-5

95-032-W2

VOL Il

April 1969