Wola NAS BARBERS POINT SCIENTIFIC 09001 Page 3 Suspended fluorescent fixtures provide Luv foot candlesat three feet above interior floor level. Roof-mounted, weather-proof fixtures illurminate the area between the building and the perimeter security fence to 0.02 foot candles at ground level. The compressor supplies filtered air at 100 psi to hoses on wall-mounted reels in the high-bays. A fire-alarm system, intercom system, and telephone service to the Loading and Maintenance Pad are provided. Building 1682 is grounded and is protected with lightning rods. rooms have static grounding points. The high-bay Substation 1684, equipped with a 750 kva, 277/480-4160 volt, 3 phase transformer, supplies power to the Assembly Building. An additional transformer, 112 1/2 kva,- 120/208-480 volt, is located within the building. A 30 kw diesel generator in the west equipment shelter functions as a backup source of power. An automatic transfer switch is provided. DRAWINGS: F 95B-080-El, E5 and E6 F 95-1682-Al thru A8 JS 95B-075-C2 95B-077-W1 and W2 F 95-1682-Cl and C2 JS 95-1682-Al.A F 95-1682-E] thru Ell and E14 JS 95-1682-A1.B F 95-1682-S]1 thru S4 JS 95-1682-A2 and A3 F 95-1682-W7 thru W12 JS 95-1682-Cl JS 95B-1682-A2 and A3 JS 95-1682-E1 JS 95B-1682-E2 and E3 JS 95-1682-W1 JS 95B-1682-Ml1 thru M3 JS 95-032-M2 JS 95B-1682-Si and $3 JS 95-032-A6 JS 95B-032-A9 and Al0 9-5 95-032-W2 VOL Il April 1969

Select target paragraph3